Day/night contactor inspection
The source of the noise and the contactor coil were checked. No significant defect or overheating was found; slight wear is suspected and replacement may be considered in the future.


A residential diagnostic visit covering a noisy day/night contactor, RCD operation, terminations, connections and the TT earthing system.
Reactive Resource attended a home in the Montmorillon area following a report of noise from the off-peak day/night contactor. The visit combined targeted fault finding with RCD tests, inspection of the bedroom light termination, tightening of four identified connectors and measurements on the TT earthing system. Customer identity and the precise address are not published.

The source of the noise and the contactor coil were checked. No significant defect or overheating was found; slight wear is suspected and replacement may be considered in the future.

The distribution board RCDs were tested, with satisfactory results at the time of the visit.

The bedroom light termination was checked, followed by inspection and tightening of four identified connectors.

External/internal loop-impedance investigation recorded a value of 194 Ω on this TT installation.

The RCD tests were satisfactory during the visit. The TT loop-impedance investigation recorded 194 Ω. A return visit is recommended and planned to investigate the earthing arrangement further and carry out appropriate work to improve the earth-loop/earthing performance, followed by repeat measurements.